Specification | | 6 min read
Metal facades and the NCC: what non-combustible actually means
How solid metal cladding satisfies C2D10, where the 1 mm coating provision applies, and why a compliant panel does not make a compliant wall.

Since the cladding failures of the last decade, every metal facade conversation in Australia now starts with fire. The good news for architects is that solid metal is one of the simpler answers in the code. The trap is assuming the panel and the wall are the same question.
Where the requirement sits
For Type A and Type B construction, NCC 2022 Volume One clause C2D10 requires external walls, and every component built into them, to be non-combustible. That is the Deemed-to-Satisfy pathway, and it is where most projects sit.
C2D10(5) lists materials that are deemed non-combustible outright. Concrete, masonry, stone, terracotta, ceramics, glass, and most common construction metals. Zinc, copper, aluminium and steel are all in that category.
So a folded metal panel is not a borderline case. It is the material the clause was written around.
The test behind it
Where a classification is needed, it comes from AS 1530.1, tested by a NATA-accredited laboratory. That is the document to ask for, and it is issued against the material rather than the system.
VMZINC classifies its zinc and copper shingles and panels A1 for reaction to fire, with PIGMENTO and lacquered finishes at A2. Archclad’s cassette and flat lock panels are tested to AS 1530.3. These are the certificates that go into a fire engineer’s file, and we can supply them for whatever we fold on your project.
The coating provision worth knowing
Pre-painted steel raises an obvious question: the steel is non-combustible, but what about the paint?
The NCC answers it directly. Pre-finished metal sheeting with a combustible surface finish not exceeding 1 mm thick, and a Spread-of-Flame Index of zero, may be used wherever a non-combustible material is required.
Colorbond, UniCote and PVDF coated aluminium all sit well inside that. The paint system on a Colorbond sheet is measured in microns, not millimetres. So a painted steel facade is not a compromise on this point, and the printed UniCote LUX finishes are in the same position.
Where compliance is actually decided
Here is the part that catches projects. A compliant panel does not make a compliant wall.
C2D10 applies to the external wall and everything built into it. On a metal facade, that means:
- The subframe or top hats behind the panel
- The membrane or sarking, which is usually a polymer
- The insulation in the cavity
- Sealants, tapes and gaskets at junctions
- Anything crossing the cavity, including fire stopping at slab edges
A solid zinc panel on a top hat frame over a combustible membrane is not automatically compliant just because the zinc is A1. The assessment is of the assembly.
This is why we do not put a blanket compliance claim on our system pages. What we can say is that the metal is non-combustible, the certificates are available, and the assembly gets confirmed per project with whoever is carrying the fire engineering.
Composite panels and why cassettes are different
The panels that caused the problem were aluminium composite: two thin aluminium skins bonded to a polyethylene core. The skins are non-combustible; the core is the fuel.
A cassette looks similar from the street and is a completely different object. It is a single folded sheet of metal, 1.5 mm thick, with nothing bonded to it. There is no core. That is worth saying explicitly in a specification, because “cassette panel” and “composite panel” get conflated by people who have only seen one of them fail.
The same applies to everything else we fold. Standing seam, snap lock, interlocking panels, shingles, flat lock and nail strip are all single sheets of metal. None of them has a laminated core.
What to ask for
If you are specifying a metal facade on a project where C2D10 applies, these are the documents worth asking for at the start rather than at handover:
- AS 1530.1 classification for the panel material, from a NATA-accredited lab
- The coating thickness and Spread-of-Flame Index, if the metal is pre-finished
- Data sheets for everything else in the cavity: membrane, insulation, tapes, sealants
- The fire engineer’s view on the assembly, not just the panel
We hold the certificates for the metals we fold and can issue them with the shop drawings. The rest of the wall usually belongs to other trades, which is exactly why it is worth naming early.
A note on BAL and bushfire
Non-combustibility under C2D10 is a different question from bushfire attack level under AS 3959. A wall can satisfy one and not the other, because BAL is about ember attack, radiant heat and flame contact on the whole assembly rather than material combustibility alone.
Metal facades perform well in BAL ratings, and UniCote LUX is rated to BAL-FZ, the highest level, but the rating attaches to the tested system, gaps and junctions included. On a bushfire prone site, the detailing around eaves, soffits and penetrations matters as much as the sheet.
If you have a project where C2D10 or a BAL rating is in play, send the wall section through with the drawings. We will tell you what we can certify and what sits with someone else. See cassette, interlocking panel and shingles for the systems most often specified on this basis, and steel for the UniCote and Colorbond ranges.